Instruction Set Quick Reference D-7
Compute Instructions
Instruction Description
Compute
CPT
Arc cosine
ACS
Addition
ADD
CPT
COMPUTE
Dest
Expression
N7:3
3
N7:4 - (N7:6 * N7:10)
If the input conditions go true, evaluate the Expression N7:4 -
(N7:6 * N7:10) and store the result in the Destination (N7:3).
The CPT instruction can perform these operations: add (+),
subtract (-), multiply (*), divide (|), convert from BCD (FRD),
convert to BCD (TOD), square root (SQR), logical and (AND),
logical or (OR), logical not (NOT), exclusive or (XOR), negate (-
)
clear (0), and move, X to the power of Y (**), radians (RAD),
degrees (DEG), log (LOG), natural log (LN), sine (SIN), cosine
(COS), tangent (TAN), inverse sine (ASN), inverse cosine (ACS
)
inverse tangent (ATN), and complex expressions (up to 80
characters)
ACS
ARCCOSINE
Source
Dest
F8:19
F8:20
0.7853982
0.6674572
If input conditions go true, take the arc cosine of the value
in F8:19 and store the result in F8:20.
always resets
sets if overflow is generated;
sets if the result is zero;
Status
C
V
Z
S
Description
Bit
otherwise resets
otherwise resets
always resets
ADD
ADD
Source A
Source B
Dest
N7:3
N7:4
N7:12
3
1
4
sets if carry is generated;
sets if overflow is generated;
sets if the result is zero;
sets if the result is negative;
When the input conditions are true, add the value in
Source A (N7:3) to the value in Source B (N7:4) and store
the result in the Destination (N7:12).
Status
C
V
Z
S
Description
Bit
otherwise resets
otherwise resets
otherwise resets
otherwise resets
Page view 306