D-22 Instruction Set Quick Reference
Program Control Instructions
Sequencer Output
SQO
Status Bits:
EN - Enable
DN - Done Bit
ER - Error Bit
When the rung goes from false-to-true, the SQO instruction
increments to the next step in the sequencer File (#N7:1). The
data in the sequencer file is transferred through a Mask (0F0F)
to the Destination (O:014) for every scan that the rung
remains true.
See page F-8 for a description of prescan operation for
this instruction.
Instruction Description
SQO
SEQUENCER OUTPUT
File
Dest
#
O:014
0F0F
R6:20
Mask
Control
Position
Length
0
4
#N7:1
Instruction Description
Master Control Reset
MCR
If the input conditions are true, the program scans the rungs
between MCR instruction rungs and processes the outputs
normally. If the input condition is false, rungs between the
MCR-instruction rungs are executed as false.
Jump
JMP
If the input conditions are true, the controller skips rungs by
jumping to the rung identified by the label (10).
Label
LBL
When the controller reads a JMP instruction that corresponds
to label 10, the controller jumps to the rung containing the label
and starts executing.
Important: Must be the first instruction on a rung.
FOR Loop
FOR
The controller executes the rungs between the FOR and the
NXT instruction repeatedly in one program scan, until it reaches
the terminal value (10) or until a BRK instruction aborts the
operation. Step size is how the loop index is incremented.
See page F-8 for a description of prescan operation for
this instruction.
Next
NXT
The NXT instruction returns the controller to the corresponding
FOR instruction, identified by the label number specified in the
FOR instruction. NXT must be programmed on an unconditional
rung that is the last rung to be repeated in a For-Next loop.
Break
BRK
When the input conditions go true, the BRK instruction aborts a
For-Next loop.
()
MCR
()
JMP
10
LBL
10
FOR
FOR
Label Number
Initial Value
0
0
N7:0
10
Index
Terminal Value
Step Size
1
NXT
NEXT
0Label Number
BRK