A-2 Specifications
Physical Specifications
Environmental
Specifications
Description Specification
LED Indicators 5 green status indicators
one for each group of 4 channels,
and one for module status
Module ID Code Class 1 Class 3
NI16V 3505 10406
NI16I 3504 10403
Recommended Cable Belden #8761 or equivalent
Maximum Wire Size Two 14 AWG wires per terminal
Maximum Cable
Impedance
NI16V Voltage Source (with less than 10
impedance): 1250
maximum loop impedance, for 1LSB error
NI16I Current Source (transmitter properly wired to its power
supply): 249
maximum loop impedance, to meet
common-mode voltage requirements
Terminal Block Removable, Allen-Bradley spare part Catalog Number
1746-RT25G
Allen-Bradley Prewired
Cables
1492-ACAB005A46, 0.5m (1.6 ft.)
1492-ACAB010A46, 1.0 m (3.3 ft.)
1492-ACAB025A46, 2.5 m (8.2 ft.)
1492-ACAB050A46, 5.0 m (16.4 ft.)
Allen-Bradley User
Terminal Blocks
1492-AIFM8-3
1492-AIFM16-F-3
Description Specification
Operating Temperature 0°C to +60°C (+32°F to +140°F) in any slot except slot 0
Storage Temperature -40°C to
+
85°C (-4F to
+
185°F)
Relative Humidity 5% to 95% (without condensation)
Agency Certification UL listed
C-UL approved
CE compliant for all applicable directives
Hazardous Environment
Classification
Class I Division 2 Hazardous Environment