6-4 Module Diagnostics and Troubleshooting
LED State Tables
Module Status LED
All LEDs
Module Status LED (Green)
The module status LED is used to indicate module-related diagnostic
or operating errors. These
non-recoverable errors
may be detected
at power-up or during module operation. Once in a module error
state, the 1746-NI16 module no longer communicates with the SLC
processor. Channel states are disabled, and data words are cleared.
Failure of any diagnostic test results in a non-recoverable error and
requires the assistance of your local distributor or Allen-Bradley.
If Module Status
LED is:
Indicated
condition:
Corrective action:
On
Proper Operation No action required.
Off
Module Fault Cycle power. If condition persists, call your
local distributor or Allen-Bradley for
assistance.
If Module
Status LED
is:
And
Channel
Status LED
is:
Indicated Condition: Corrective action:
On
On
Channel Enabled No action required.
Blinking
Open-Circuit Condition To determine the exact error, check the error
bits in the input image bits (15 through 13).
Check the channel configuration word for
valid data. Make sure that the data format is
indicated correctly in status bits. Class 1 data
format status bits are bits 5 and 4. Class 3
data format status bits are bits 6-4. See the
“Troubleshooting Flowchart” on page 6-6 and
Chapter 5 for more information.
Out-of-Range Condition
Channel Configuration
Error
Off
Power-Up No action required.
Channel Not Enabled No action required. For an example showing
how to enable a channel, see Chapter 2,
Quick
Start
, or Chapter 7,
Application Examples
.