ControlNet Objects C-19
N-Files (Continued)
Important: If your controller or HMI platform supports CIP messaging,
use the CIP Parameter object to get and set parameters.
PCCC Object (Continued)
N-File Description
N10 – N18 These N-files let you read and write parameter values in the drive and the
adapter.
Single Mode Multi-Drive Mode
N10:0
N10:1 – 999
Number of parameters in the drive
Drive parameters 1 – 999
Number of parameters in Drive 0
Drive 0 parameters 1 - 999
N11:0 – 999 Drive parameters 1000 – 1999 Drive 0 parameters 1000 - 1999
N12:0 – 999 Drive parameters 2000 – 2999 Drive 0 parameters 2000 - 2999
N13:0 Number of parameters in this
adapter
Number of parameters in this
adapter
N13:1 – 999 Parameters 1 – 999 in this adapter Parameters 1 – 999 in this adapter
N14:0 Number of parameters in this
adapter
Number of parameters in Drive 1
N14:1 – 999 Parameters 1 – 999 in this adapter Drive 1 parameters 1 – 999
N15:0 Number of parameters in the slave Number of parameters in Drive 2
N15:1 – 999 Parameters 1 – 999 in the slave Drive 2 parameters 1 – 999
N16:0 Not supported Number of parameters in Drive 3
N16:1 – 999 Not supported Drive 3 parameters 1 – 999
N17:0 Not supported Number of parameters in Drive 4
N17:1 – 999 Not supported Drive 4 parameters 1 – 999
N18:0 Not supported Number of parameters in this
adapter
N18:1 – 999 Not supported Parameters 1 – 999 in this adapter