RFID Tag Speed Chapter 12
When the interface receives a stop command, Command 6, it will revert back to
the normal mode of operation and resume the polling cycle. Continuous Read
mode can also be canceled by issuing a channel reset (reset bit in the output image
word set to 1).
When using a 50 mm disc tag, Cat. No. 56RF-TR-8090 transceiver, and reading
4 bytes of data it may be possible to achieve a line speed of up to 3 m/s.
Modes of Operation
Only one type of mode of operation can be used on each channel. To change
modes you will need to issue a Stop Continuous Read, and then reissue a Start
Continuous Read with the new mode. Both channels can be setup for the same
mode or different modes simultaneously. Modes of operation are limited based
on the model number of the interface.
56RF-IN-IPS12
1 RFID Channel (Channel 0)
1 discrete input and 1 discrete output
Support modes 0 and 1 only
56RF-IN-IPD22
2 RFID Channels (Channel 0, Channel 1)
1 discrete input and 1 discrete output
Support modes 0, and 1 only.
The single input can be used for either channel.
56RF-IN-IPD22A
2 RFID Channels (Channel 0, Channel 1)
2 discrete inputs
Support modes 0, 1, 2, and 3
The same input can be used for either channel.