7-4 Troubleshooting
Net A Status Indicator
Status Cause Corrective Action
Off The module is not
powered, the module is not
connected properly to the
network, or the module
needs an IP address.
Securely connect the module to the drive using a
1202-Cxx Communication cable.
Securely connect the Ethernet cable to the Ethernet
connector.
Set a unique IP address using a BOOTP server or
by disabling BOOTP and using parameters.
Apply power to the drive and module.
Solid Red The module failed
duplicated IP address
detection test.
Configure the module to use a unique IP address and
cycle power.
Flashing Red An EtherNet/IP connection
has timed out.
Place the controller in RUN mode, or apply power to
the peer device that will send I/O.
Check the amount of traffic on the network.
Flashing Red/
Green
The module is performing
a self-test.
No action required.
Flashing Green The module is properly
connected but is not
communicating with any
devices on the network.
Place the controller in RUN mode, or apply power to
the peer device that will send I/O.
Program a controller or peer device to recognize
and transmit I/O or make a messaging connection to
the module.
Configure the module for the program in the
controller or the I/O from the peer device.
Solid Green The module is properly
connected and
communicating on the
network.
No action required.