Publication 1747-UM005B-EN-P - March 2006
2-2 Quick Start
Procedures
Unpack the Module
Remove the items from the package making sure that the contents
include:
DH-485/RS-232C Interface Module (catalog number 1747-KE).
cable (1747-C13).
installation instructions, publication 1747-IN006.
If the contents are incomplete, call your local Rockwell Automation
representative for assistance.
Install the Module
Install the module and configure the SLC chassis. The following steps
summarize these procedures.
1. Choose the module’s functionality.
2. Select the configuration method you want to use and place your
module in the corresponding mode using JW4.
3. Set your CONFIG and DF1 ports using JW1 and JW2.
4. Configure your SLC chassis using RSLogix 500 software.
5. Configure the module.
6. If your module is still in Configuration mode, place it in Run
mode using the JW4 jumper.
7. Connect your DH-485 and DF1 cabling.
8. Turn on power and verify module status.
For more information refer to Chapter 4 (Installation and System
Configuration).
ATTENTION
Do not install or remove the 1747-KE module from
the SLC chassis until all power dissipates from the
SLC 500 power supply (approximately 10 seconds).