Publication 1747-UM005B-EN-P - March 2006
Module Configuration Using an ASCII Terminal 5-5
When you enter a valid value the prompt line disappears,
indicating that your change has been saved. You now have the
option to select another parameter.
3. Once you finish changing parameters, press [X] to return to the
Top Level Setup Menu.
CONFIG Port Menu
The CONFIG PORT Setup Menu provides six selections.
CONFIG Port Setup Menu
CONFIG PORT Setup Parameters
Whenever the module is powered up, the CONFIG port is set to the
default parameters. If these parameters are changed and the setup is
saved, they will remain changed only as long as module power
remains on. Whenever power to the module is cycled off, the
CONFIG port parameters return to their default values.
CONFIG PORT Setup Parameters
CONFIG
PORT
Setup Menu
1. Baudrate
2. Bits per character
3. Parity
4. Stop bits
5. Handshaking
X. SA
VE AND EXIT
Enter Selection. . . . .
Parameter Default Options Description
Communication Rate 1200 300, 600, 1200, 2400,
4800, 9600, 19200
The speed in bits per second at which data is transferred.
Must be set the same as the ASCII terminal.
Bits Per Character 8 7, 8 The size in number of bits of each character to be
transferred. Must be set the same as the ASCII terminal.
Parity None Even, Odd, None Used for checking data during the transfer. Must be set the
same as the ASCII terminal.
Stop Bits 1 1, 2 Used for delineating data during the transfer. Must be set
the same as the ASCII terminal.
Handshaking Software None, Software,
Hardware, Both
Describes the communication protocol. If Hardware
handshaking or Both is selected, you must use cables
wired accordingly.