Circuit Breakers
The “non-” listings in the following tables include inverse time circuit breakers,
instantaneous trip circuit breakers (motor circuit protectors) and 140M self-
protected combination motor controllers. If one of these is chosen as the desired
protection method, the following requirements apply:
IEC – Both types of circuit breakers and 140M self-protected
combination motor controllers are acceptable for IEC installations.
UL - Only inverse time circuit breakers and the specified 140M self-
protected combination motor controllers are acceptable for UL
installations.
(1) Typical designations include, but may not be limited to the following; Parts 1 & 2: AC, AD, BC,
BD, CD, DD, ED, EFS, EF, FF, FG, GF, GG, GH.
Table 12 - 208 Volt AC Input Frames 1…6 Drive Protection Devices
Drive
Cat. No.
Frame
kW Rating Input
Ratings
Dual Element
Time Delay Fuse
Non-Time Delay
Fuse
Circuit
Breaker
(3)
Motor
Circuit
Protector
(5)
140M Motor Starter with Adjustable Current Range
(6)(7)
ND HD Amps kVA Min
(1)
Max
(2)
Min
(1)
Max
(2)
Max
(4)
Max
(5)
Available Cat. No.s
(8)
Minimum Enclosure
Volume (in.
3
)
(9)
20DB4P2 1 0.75 0.55 3.7 1.3 6 10 6 17.5 15 7 M-C2E-B63 M-D8E-B63 7269
20DB6P8 1 1.5 1.1 6.8 2.4 10 15 10 30 30 15 M-C2E-C10 M-D8E-C10 M-F8E-C10 7269
20DB9P6 1 2.2 1.5 9.5 3.4 12 20 12 40 40 15 M-C2E-C16 M-D8E-C16 M-F8E-C16 7269
20DB015 1 4.0 3.0 15.7 5.7 20 35 20 70 70 30 M-C2E-C20 M-D8E-C20 M-F8E-C20 7269
20DB022 1 5.5 4.0 23.0 8.3 30 50 30 100 100 30 M-D8E-C25 M-F8E-C25 7269
20DB028 2 7.5 5.5 29.6 10.7 40 70 40 125 125 50 M-F8E-C32 7269
20DB042 3 11 7.5 44.5 16.0 60 100 60 175 175 70 M-F8E-C45 13630
20DB052 3 15 11 51.5 18.6 80 125 80 200 200 100
20DB070 4 18.5 15 72 25.9 90 175 90 300 300 100
20DB080 4 22 18.5 84.7 30.5 110 200 110 350 350 150
20DB104 5 30 113 40.7 150 250 150 475 350 150
22 84.7 30.5 125 200 125 350 300 150
20DB130 5 37 141 44.1 175 275 175 500 375 250
30 113 35.3 125 225 125 400 300 150
20DB154 6 45 167 60.1 225 350 225 500 500 250
37 141 50.9 200 300 200 500 450 250
20DB192 6 55 208 75.0 300 450 300 600 600 400
45 167 60.1 225 350 225 500 500 250
20DB260 6 66 255 96.7 300 575 300 750 750 400
55 199 71.7 225 450 225 600 600 400
(1) Minimum protection device size is the lowest rated device that supplies maximum protection without nuisance tripping.
(2) Maximum protection device size is the highest rated device that supplies drive protection. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(3) Circuit Breaker - inverse time breaker. For US NEC, minimum size is 125% of motor FLA. Ratings shown are maximum.
(4) Maximum allowable rating by US NEC. Exact size must be chosen for each installation.
(5) Motor Circuit Protector - instantaneous trip circuit breaker. For US NEC minimum size is 125% of motor/drive FLA. Ratings shown are suggested. Instantaneous trip settings must be set to US NEC code. Not to exceed 1300% FLA.
(6) Bulletin 140M with adjustable current range should have the current trip set to the minimum range that the device will not trip.
(7) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/ 347. Not UL listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground
systems.
(8) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See Bulletin 140M Motor Protection Circuit Breakers Application Ratings
.
(9) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated enclosure with the minimum volume specified in this column. Application specific thermal
considerations may require a larger enclosure.
Page view 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 79 80

Comments to this Manuals

No comments