54 Rockwell Automation Publication 20D-IN024C-EN-P - July 2013
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
Figure 17 - Main Control Board Dip Switches
Hardware Enable Circuitry
By default, digital input 6 is configured for hardware enable input. This is for
applications requiring the drive to be disabled without software interpretation.
With the “HW Enable Jumper (Shunt)” on the pins closest to the circuit board
(2-4), digital input 6 is configured as a “dedicated” hardware enable. If this
configuration is not required, the “HW Enable Jumper (Shunt)” may be moved
to the out board pins (1-3), making digital input 6 user programmable via
parameter 830 [Dig In6 Sel]. See Figure 17
on page 54.