Rockwell Automation Publication 20D-IN024C-EN-P - July 2013 57
PowerFlex 700S Adjustable Frequency AC Drive - Phase II Control
I/O Wiring Examples
Table 27 - TB1 Analog Input/Output and Encoder Wiring Examples
Input/Output Connection Example Required Parameter Changes
Potentiometer Unipolar Speed Reference
0…10V Analog Input
Internal Source
NA
Potentiometer Bi-polar Speed Reference
±10V Analog Input
Internal Source
NA
Unipolar Speed Reference
0…10V Analog Input
External Source
NA
Analog Speed and Current Meters
±10V DC Analog Outputs
Using Analog Output 1: ±10V to meter Motor RPM and direction:
Send the data to the Analog Output parameter:
Par 833 [Anlg Out1 Real] (the destination) linked to Par 71 [Filtered
SpdFdbk] (the source)
Scale the output to the source parameter:
Par 835 [Anlg Out1 Scale] = 175 (Par 4 [Motor NP RPM] = 1750 /
10V)
Using Analog Out 2: ±10V to meter Motor Current:
Send the data to the Analog Output parameter:
Par 840 [Anlg Out2 Real] (the destination) linked to Par 308 [Output
Current] (the source)
Scale the output to the source parameter:
Par 822 [Anlg Out2 Scale] = xx (Par 2 [Motor NP FLA] / 10V output)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
-Signal or Source Common
+Signal
Shield / Common
1
2
3
4
5
6
7
8
9
10
11
12
-
+
-
+
1
2
3
4
5
6
7
8
9
10
11
12
Page view 56
1 2 ... 52 53 54 55 56 57 58 59 60 61 62 ... 79 80

Comments to this Manuals

No comments