Publication 2705-UM001A-EN-P
Overview of RediSTATION 1-5
LED Indicator
The RediSTATION has one bicolor LED (red/green) to show its
operating status. The LED shows the following indications.
The LED is visible when the cover of the enclosure is removed.
DIP Switches
The RediSTATION has one 10-position DIP switch for setting:
DeviceNet Node Address
DeviceNet Data Rate
Output Fault State (Off or Last State)
Output Flash Rate
The DIP switch is located on the circuit board inside the enclosure.
The switch settings and functions are shown below. The default
setting for each switch or group of switches is underlined.
Color State Indication
None Off No power
Red Solid Unrecoverable fault
Flashing Output error or configuration error
Green Solid Normal runtime operation
The RediSTATION device is operating
as a slave to the master controller.
Flashing Device is idle or not allocated to a
master.
1
2345678910
Default Configuration
OFF = 0
ON = 1
DeviceNet Address 000000 - 111111 (0 to 63)
DeviceNet Data Rate
00
= 125K BPS
01 = 250K BPS
10 = 500K BPS
11 = Invalid
Output Fault State
0
= Outputs Turn Off on Fault
1 = Outputs Hold Last State on Fault
Output Flash Rate
0
= 1 Hz (0.5 sec On, 0.5 sec Off)
1 = 2 Hz (0.25 sec On, 0.25 sec Off)