Rockwell-automation 284A ArmorStart with ArmorPoint Backplane - Gettin User Manual Page 16

  • Download
  • Add to my manuals
  • Print
  • Page
    / 40
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 15
16
Publication 284A-QS001C-EN-P - July 2006
LED Status Indication The LED Status Indication provides 4 status LEDs and a Reset button. The
LEDs provide status indication for the following:
POWER LED
The LED is illuminated solid green when control power is present and
with the proper polarity
•RUN LED
This LED is illuminated solid green when a start command and control
power are present
NETWORK LED
This bi-color (red/green) LED indicates the status of the
communication link
FAULT LED
Indicates Controller Fault (trip) condition
The “Reset Button” as a local trip reset.
Figure 10 LED Status Indication and Reset
ArmorStart with ArmorPoint ArmorStart for the ArmorPoint Backplane
The Bulletin 284A ArmorStart Distributed Motor Controller allows
connectivity to the ArmorPoint backplane. The ArmorPoint I/O system can
communicate using DeviceNet™, ControlNet™, or EtherNet
communication protocols. In addition to the other network communication
protocols; the ArmorPoint Distributed I/O products allow the I/O capability
to be expanded beyond the standard two outputs. Two dual-key relay output
connectors are provided standard. The outputs are sourced from control
voltage power (A1, A2). LED status indication is also provided, as standard
with the ArmorPoint. When using ArmorPoint, a maximum of two
ArmorStart Distributed Motor Controllers can be connected to the
ArmorPoint Distributed I/O products.
ArmorStart to ArmorPoint Connectivity
Figure 11 Connectivity Diagram for one ArmorStart Distributed Motor Controller
Page view 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 39 40

Comments to this Manuals

No comments