27
Bulletin 284 Pararmeters
Table 4 Basic Program Group for Sensorless Vector Performance
Stop drive before changing this parameter.
See Important below:
Parameter
Number
Parameter
Description
Display/
Options
Min./
Max.
Defaults
Settings
131 Motor NP Volts 1 VAC
20/Drive Rated
Volts
Based on
Driving
Rating
132 Motor NP Hz 1 Hz 10/240 Hz 60 Hz
133
Motor OL
Current
0.1 A
0.0/(Drive Rated
Amps x 2)
Based on
Driving
Rating
134 Minimum Freq. 0.1 Hz 0.0/240 Hz 0.0 Hz
135
Maximum
Freq.
0.1 Hz 0.0/240 Hz 60 Hz
136 Start Source
0 = Keypad
1 = 3-Wire
2 = 2-Wire
3 = 2-W Lvl Sens
4 = 2-W Hi Speed
5 = Comm Port
0/5 5
137 Stop Mode
0 = Ramp, CF
1 = Coast, CF
2 = DC Brake, CF
3 = DCBrkAuto, CF
4 = Ramp
5 = Coast
6 = DC Brake
7 = DC BrakeAuto
0/7 0
138
Speed
Reference
0 = Drive Pot
1 = InternalFreq
2 = 0…10V Input
3 = 4…20 mA Input
4 = Preset Freq
5 = Comm Port
0/5 5
139 Accel Time 1 0.1 Secs 0.0/600.0 Secs 10.0 Secs
140 Decel Time 1 0.1 Secs 0.0/600.0 Secs 10.0 Secs
141
Reset to
Default
0 = Ready/Idle
1 = FactoryRset
0/1 0
IMPORTANT
These drive parameters options will cause the
Bulletin 284 ArmorStart Distributed Motor Controller to
become disabled.
Page view 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 39 40

Comments to this Manuals

No comments