Specifications Appendix A
Table 3 - Output and Trip Relay Ratings
Terminals
OUT A:
OUT B (E3 Plus):
Trip Relay:
13/14
23/24
95/96
Type of Contacts Form A
SPST - NO
Rated Thermal Current (I
the
)5 A
Rated Insulation Voltage (U
i
)300V AC
Rated Operating Voltage (U
e
)240V AC
Rated Operating Current (I
e
) 3 A (@120V AC), 1.5 A (@240V AC)
0.25 A (@110V DC), 0.1 A (@220V DC)
Minimum Operating Current 10 mA @ 5V DC
Rating Designation B300
Utilization Category AC-15
Resistive Load Rating (p.f. = 1.0) 5 A, 250V AC
5 A, 30V DC
Inductive Load Rating (p.f. = 0.4)
(L/R = 7 ms)
2 A, 250V AC
2 A, 30V DC
Short Circuit Current Rating 1,000 A
Recommended Control Circuit Fuse KTK-R-6
(6 A, 600 V)
Rated Number of Operations
Trip Relay:
OUT A and B:
W/100-C09…100-C43
W/100-C60…100-C85
W/NEMA Size 0…2
W/NEMA Size 3
100,000
5,000,000
2,500,000
1,000,000
300,000
Table 4 - Input Ratings
Terminals
IN 1:
IN 2:
IN 3 (E3 Plus):
IN 4 (E3 Plus):
Supply Voltage (24V DC):
1
2
3
4
5,6
Supply Voltage
(provided by E3)
24V DC ± 10%
Type of Inputs Current Sinking
On-State Voltage 15V DC
On-State Current (turn-on) 2 mA
Steady State Current 8 mA
Off-State Voltage 5V DC