Rockwell-automation 193-EC4 EC4 Current Monitoring Relay User Manual User Manual Page 22

  • Download
  • Add to my manuals
  • Print
  • Page
    / 157
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 21
Rockwell Automation Publication 193-UM011A-EN-P - September 2010 23
Installation and Wiring Chapter 2
Figure 9 - Wire Size and Torque Specifications
Power Terminals
Table 2 - Power Terminal Wire Size and Torque Specification
Cat. No.
193-EC
_ _B, -EC_ _D 193-EC_ _E
Stranded/Solid
AWG
Single Conductor
Torque
Multiple
Conductor
Torque
#14...6 AWG
22 lb-in
#10...6 AWG
30 lb-in
#12...1 AWG
35 lb-in
#6...2 AWG
35 lb-in
Flexible-Stranded with
Ferrule
Metric
Single Conductor
Torque
Multiple
Conductor
Torque
2.5...16 mm
2
2.5 N•m
6...10 mm
2
3.4 N•m
4...35 mm
2
4 N•m
4...25 mm
2
4 N•m
Coarse-Stranded/Solid
Metric
Single Conductor
Torque
Multiple
Conductor
Torque
2.5...25 mm
2
2.5 N•m
6...16 mm
2
3.4 N•m
4...50 mm
2
4 N•m
4...35 mm
2
4 N•m
A
B
M
N
P
C
L
K
D
E
E
F
I
G
H
J
0
2
4
6
8
0
2
4
6
8
Page view 21