96 Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 8 Trip History and Snapshot
SS L2 Current
This parameter reports the value of L2
Current at the time of the last relay trip.
Parameter Number 145
Access Rule Get
Data Type INT
Object Mapping 0Fhex-91-01
Group Trip Snapshot
Units Amps
Minimum Value 0
Maximum Value 32767
Default Value —
SS L3 Current
This parameter reports the value of L3
Current at the time of the last relay trip.
Parameter Number 146
Access Rule Get
Data Type INT
Object Mapping 0Fhex-92-01
Group Trip Snapshot
Units Amps
Minimum Value 0
Maximum Value 32767
Default Value —
SS GF Current
This parameter reports the value of ground
fault current at the time of the last relay
trip.
Parameter Number 148
Access Rule Get
Data Type INT
Object Mapping 0Fhex-94-01
Group Trip Snapshot
Units Amps
Minimum Value 0
Maximum Value 1275
Default Value —