Rockwell Automation Publication 193-UM011A-EN-P - September 2010 145
DeviceNet Information Appendix B
ODVA Fault Codes
The following ODVA fault codes are returned by the Control Supervisor Object
instance attribute 13 “TripCode:”
13 Get/Set COS Mask WOR
D
0 Change of state mask for
DeviceNet
15 Get/Set AutoBaudEnabl
e
BOOL 0…1 1 1 = Enabled
16 Get/Set Output
Assembly
USINT 2, 101, 103,
104, 105,
140
103 Output Assembly
instance that is active
17 Get/Set Input Assembly USINT 50, 51, 100,
106, 107,
141, 184
100 Input Assembly instance
that is active
18 Get/Set Program Lock BOOL 0…1 0 0 = Unlocked
1 = Locked
19 Get/Set Set To Defaults BOOL 0…1 0 0 = No action
1 = Reset
20 Get Device
Configuration
WOR
D
0…7 Bit 0 set = 4 in/2 out
hardware present
Bit 1 set = PTC hardware
present
Bit 2 set = Ground Fault
hardware present
50 Get/Set PNB COS Mask WOR
D
0…0xFF 0 Change of State mask
for PNB
Table 64 - DeviceNet Interface Object Common Services
Service
Code
Implemented for: Service
Name
Class Instance
0x0E No Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
Table 63 - DeviceNet Interface Object Instance Attributes
Attribute
ID
Access
Rule
Name Data
Typ e
Min/Max Defau
lt
Desc.
Table 65 - ODVA Fault Codes
Trip Code Description Trip Code Description
62 Memory Fault 73 Starts/Hour Exceeded
10 Test Trip 102 Comm Fault
11 Remote Trip 103 Comm Idle Fault
23 L1 Loss 108 L2 Undercurrent
24 L2 Loss 109 L3 Undercurrent
25 L3 Loss 110 L1Overcurrent
27 Ground Fault 111 L2Overcurrent