Publication 2711-UM014G-EN-P - September 2008 219
Terminal Connections Chapter 12
Connecting to an SLC, PLC-5, ControlLogix, MicroLogix 1500LRP,
CompactLogix, or FlexLogix
Directly connect the PanelView 300 Micro terminal to an SLC, PLC-5
ControlLogix, MicroLogix 1500LRP, CompactLogix, or FlexLogix
processor using the following cables. Use DH-485 (SLC only) or DF1
protocols for communication.
RS-232 Communication Port
Cable, Catalog No. 1761-CBL-AP00, Series C (.5 m, 1.5 ft)
Cable, Catalog No. 1761-CBL-PM02, Series C (2 m, 6.5 ft)
Cable, Catalog No. 2711-CBL-PM05, Series C (5 m, 15 ft)
Cable, Catalog No. 2711-CBL-PM10, Series C (10 m, 30 ft)
1
3
2
5
4
8
7
6
PanelView 300 Micro
RS-232 Connector
Pin #
9
1 24V
2
3
GND
RTS
Pin #
SLC
1
5
6
9
ControlLogix Module
5
7
8
1
2
3
4
6
6 CTS
5 DCD
4 RXD
7 TXD
8 GND
RI
GND
RTS
CTS
DCD
RXD
TXD
DTR
DSR
1761-CBL-AP00
1761-CBL-PM02
2711-CBL-PMxx
Cable Connector
Cable Connector
8-Pin Mini-DIN
9-Pin D-Shell