Chapter 2 Applying Power and Resetting Terminal
Hazardous Location
Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, D; Class II, Division 2, Groups F and G; Class III; or non-hazardous
locations only. The following WARNING statement applies to use in
hazardous locations.
See the nameplate on terminal for hazardous locations certifications.
WARNING
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I, Class
II, Class III Division 2.
Do not replace components or disconnect equipment unless power
has been switched off or the area is known to be non-hazardous.
Do not connect or disconnect components unless power has been
switched off or the area is known to be non-hazardous.
This product must be installed in an enclosure. All cables
connected to the product must remain in the enclosure or be
protected by conduit or other means.
All wiring must comply with N.E.C. article 501-4(b), 502-4(b),
503-3(b) as appropriate.
ATTENTION
In Class I, Class II, Class III Division 2 Hazardous locations,
the PanelView terminal must be wired per the National
Electric Code as it applies to hazardous locations. Peripheral
equipment must also be suitable for the location in which it is
installed.