Rockwell-automation 2711 Standard PanelView Operator Terminal User Man User Manual Page 255

  • Download
  • Add to my manuals
  • Print
  • Page
    / 292
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 254
Publication 2711-UM014G-EN-P - September 2008 255
Messages, Codes and Self-test Numbers Appendix B
ControlNet Terminal Messages
See Terminal Codes for messages below
Error Number Terminal
Messages
Type Meaning Recommended Action
634 PanelView offline Comm Warning PanelView is offline. Check connections
634 Write fail. Comm Warning PanelView is communicating with the
controller. The data table address
does not exist.
Check / define data table address in
the controller.
634 Write timeout. Comm Warning PanelView is not communicating with
the logic controller.
Check connections and node
configuration in the application.
634 Read fail. Comm Warning PanelView is communicating with the
controller. The data table address
does not exist.
Check/define data table address in
the controller.
634 Read timeout. Comm Warning PanelView is not communicating with
the controller.
Check/define data table address in
the controller.
636 Initial write
failed.
Reminder Write to Logic Controller on Startup
was configured and on powerup, the
PanelView could not write initial
values to a node's data table address.
or
Write to Logic Controller on Startup
was not configured and the
PanelView was unable to write a
controller. Note: The error is only
displayed on the first write attempt.
Check/define data table address in
the controller.
Check communication connections
and node configuration in the
application.
Page view 254
1 2 ... 250 251 252 253 254 255 256 257 258 259 260 ... 291 292

Comments to this Manuals

No comments