EtherNet/IP Objects C-17
N-Files (Continued)
PCCC Object (Continued)
N-File Description
N42 This N-file lets you read and write some values configuring the
port.
N42:3 Time-out (read/write): Time (in seconds) allowed between
messages to the N41 file. If the module does not receive a
message in the specified time, it performs the fault action
configured in its [Comm Flt Action] parameter.
N42:7 Module Port Number (read only): SCANport port on the drive to
which the module is connected.
N50:1 – N50:249
N51:0 – N51:249
N52:0 – N52:249
N53:0 – N53:249
N54:0 – N54:249
N55:0 – N55:249
N56:0 – N56:249
N57:0 – N57:249
N58:0 – N58:249
N59:0 – N59:249
N60:0 – N60:249
N61:0 – N61:249
SCANport Product
(1)
Parameter Value Read/Write
(Parameters 1 – 2999)
(1)
SCANport Product refers to a drive or other SCANport product connected to the
module.
N90:1 – N90:249
N91:0 – N91:249
N92:0 – N92:249
N93:0 – N93:249
N94:0 – N94:249
N95:0 – N95:249
N96:0 – N96:249
N97:0 – N97:249
N98:0 – N98:249
N99:0 – N99:249
N100:0 – N100:249
N101:0 – N101:249
SCANport Product
(1)
Parameter Full/All Information Read
(Parameters 1 – 2999)
(Each file contains a maximum of 250 parameters)