Publication 1746-UM001A-US-P
Quick Start for Experienced Users 2-3
3. Insert the 1746-NI16 module into the chassis. Reference
ATTENTION
!
Never install, remove, or wire modules with power applied to the chassis or devices
wired to the module.
Make sure system power is off; then insert the module into your 1746 chassis.
In this example procedure, local slot 1 is selected. Any slot may be used except 0.
Chapter 3
(Installation and
Wiring)
Top and Bottom
Module Releases
Card
Guide
4. Connect sensor cable. Reference
Connect sensor cable to the module’s terminal block.
Important:
Follow these guidelines when wiring the module:
Use shielded communication cable (Belden8761) and keep length as short as possible.
Connect only one end of the cable shield to earth ground.
Connect all the shields to the earth ground at the SLC 500™ chassis mounting tab.
Single-ended source commons may be jumpered together at the terminal block.
Channels are not isolated from each other. All analog commons are connected together internally.
Common mode voltage range is ±10.25 volts. The voltage between any two terminals must be less than
20.5 volts.
The module does not provide power for the analog input transmitters or sensors.
Use a power supply that matches the transmitter (sensor) specifications.
Chapter 3
(Installation and
Wiring)
Sensor Cable
Terminal Block
IN 0
IN 2
IN 4
IN 6
IN 1
IN 3
IN 5
IN 7
Analog Com
Analog Com