Rockwell Automation Publication 193-UM002I-EN-P - December 2011 105
Chapter
5
Programmable Parameters
Introduction
This chapter describes each programmable parameter and its function.
Programming
Refer to Chapter 4 for instructions in using RS NetWorx for DeviceNet to
modify parameter settings and Input and Output Assemblies.
Program Lock
Program Lock, Parameter 53, provides a degree of security from having parameter
settings unintentionally altered when programmed to the “locked” setting.
Reset to Default Factory Settings
Set to Defaults, Parameter 54, allows the installer to reset all parameter settings
(including trip logs) to the factory default values.
Parameter Group Listing
The E3 Overload Relay can contain up to 13 parameter groups, depending on the
model number and firmware revision. In this chapter, the following parameter
groups will be discussed:
IMPORTANT
Parameter setting changes downloaded to the E3 Overload Relay take
effect immediately, even during a “running” status.
IMPORTANT
Parameter setting changes made in a configuration tool, (e.g.,
RSNetWorx for DeviceNet) do not take effect in the E3 Overload Relay
until the installer applies or downloads the new settings to the device.
IMPORTANT
Resetting to factory default values also resets the E3 Overload Relay’s
DeviceNet node address (MAC ID) to the default value of 63.
Monitor Group
Overload Setup
Reset/Lock Groups
Advanced Setup
DeviceNet Setup
Output Setup
DeviceLogix Setup