Rockwell Automation Publication 193-UM002I-EN-P - December 2011 239
DeviceNet™ Information Appendix B
Table 99 - Assembly Object Instance 142 EC5 DeviceLogix Input Assembly
Table 100 - Assembly Object Instance 184 Data Format PNB STATUS
Connection Object – Class
Code 0x05
Multiple instances of the Connection Object are supported. Instance 1 is the
explicit message connection, instance 2 is the polled I/O connection, instance 4 is
the Change of State/Cyclic I/O connection, and instances 5-7 are available for
explicit UCMM connections.
The following Instance 1 (explicit message connection) attributes are supported.
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Input 4 Input 3 Input 2 Input 1 Out B Stat Out A Stat Warning Tripped
0 Input 6 Input 5
1Network
Output 7
Network
Output 6
Network
Output 5
Network
Output 4
Network
Output 3
Network
Output 2
Network
Output 1
Network
Output 0
2 DLogix
Enabled
Network
Output 14
Network
Output 13
Network
Output 12
Network
Output 11
Network
Output 10
Network
Output 9
Network
Output 8
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0Network
Output 7
Network
Output 6
Network
Output 5
Network
Output 4
Network
Output 3
Network
Output 2
Network
Output 1
Network
Output 0
1 DLogix
Enabled
Network
Output 14
Network
Output 13
Network
Output 12
Network
Output 11
Network
Output 10
Network
Output 9
Network
Output 8