Rockwell Automation Publication 193-UM002I-EN-P - December 2011 171
Power Parameters Chapter 8
Power Setup Group
PW Trip Enable
This parameter allows the installer to
enable or disable power based trip
functions separately.
1 = Trip
0 = No TrIp
Parameter Number 225
Access Rule Get/Set
Data Type UINT
Object Mapping 0Fhex-E1-01
Group Power Setup
Units
Minimum Value
Maximum Value
Default Value
Bit Function:
1514131211109876543210
XUnder Real Pwr
XOver Real Pwr
X Under Con kVAR
XOver Con kVAR
X Under Gen kVAR
XOver Gen kVAR
XUnder Power kVA
X Over Power kVA
X Under PF Lagging
XOver PF Lagging
XUnder PF Leading
XOver PF Leading
X Power Overflow
PW Warn Enable
This parameter allows the installer to
enable or disable power based warning
functions separately.
1 = Warning
0 = No Warning
Parameter Number 226
Access Rule Get/Set
Data Type UINT
Object Mapping 0Fhex-E2-01
Group Power Setup
Units
Minimum Value
Maximum Value
Default Value
Bit Function:
1514131211109876543210
XUnder Real Pwr
XOver Real Pwr
X Under Con kVAR
XOver Con kVAR
X Under Gen kVAR
XOver Gen kVAR
XUnder Power kVA
X Over Power kVA
X Under PF Lagging
XOver PF Lagging
XUnder PF Leading
XOver PF Leading
X Power Overflow