Rockwell-automation 193-EC1_2_3_5, 193-ECPM,592-EC1_2_3_5 E3 and E3 Pl User Manual Page 225

  • Download
  • Add to my manuals
  • Print
  • Page
    / 276
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 224
Rockwell Automation Publication 193-UM002I-EN-P - December 2011 225
Appendix
A
Specifications
Electrical Specifications
Exception: Any E3 Overload Relay that uses an external ground fault sensor is limited to 50/60 Hz detection.
Figure 13: E3 & E3 Plus Power Supply Current
Figure 3: Motor/Load Ratings
Terminals 1/L1, 3/L2, 5/L3, 2/T1, 4/T2, 6/T3
Rated Insulation Voltage (U
i
)690V AC
Rated Operating Voltage (U
e
)
IEC:
UL:
690V AC
600V AC
Rated Impulse Voltage (U
imp
)6 kV
Rated Operating Current (I
e
) See Catalog Number Explanation
Rated Frequency 20...250 Hz
Short Circuit Ratings See Chapter 2
Number of Poles 3
Application Single-phase or Three-phase
Table 16: Power Supply Ratings
Terminals DeviceNet Connector: V+ (Red), V- (Black)
Rated Supply Voltage (U
s
)24V DC
Operating Range 11...25V DC
Rated Supply Current See Chart Below
Maximum Surge Current at Power-Up 3 A
Maximum Power Consumption
E3:
E3 Plus:
3.2 W
4.2 W
Maximum Power Interruption Time
@ 11V DC:
@ 25V DC:
1 ms
10 ms
E3 & E3 Plus Supply Current
0
50
100
150
200
250
300
350
10 15 20 25 30
Input Voltage (V)
Input Current (mA)
E3 Plus
E3
Page view 224
1 2 ... 220 221 222 223 224 225 226 227 228 229 230 ... 275 276