42 Rockwell Automation Publication 56RF-UM001A-EN-P - October 2011
Chapter 4 EtherNet/IP Addressing
Click File > Save As to save the relationship, if desired.
Cycle the power to the Bul. 56RF interface block. You should no longer see the
Bul. 56RF interface block appear in the Request History panel.
From a DOS prompt, you can ping the new address. The response should be 4
packets sent, 4 packets received and 0 lost.
Change IP Address from One
Advanced Address to another
Advanced Address
The easiest way to change the IP Address from one non-simple address to another
non-simple address is to use RSLinx. In this case, the three network switches on
the Bul. 56RF interface block are set to 999, and the address has been previously
set using the BootP/DHCP server. The example below shows how to change the
IP address from 192.168.2.115 to 192.168.3.115.
Open RSLinx.
1. Click on the RS-Who icon.
2. Expand the EtherNet connection.
3. Right click on the RFID Adaptor.
4. Click Module Configuration.
Page view 41