96 Publication 2711P-QS001A-EN-P - October 2007
Chapter 7 Qualify the Runtime Application
Test Run Graphic Displays
FactoryTalk View ME software provides a Test Display mode to test
the animation and assigned tags connected to objects in a graphic
display. Any information, warning, or errors are logged to the
diagnostic list for your review.
Test Display mode tests all objects in a display:
Button objects
Numeric and string object to verify that correct values are
displayed
Objects that require user input
Objects that use animation
For each object tested, review and correct any errors and warnings
logged to the diagnostic list. Retest the display object before
proceeding to the next object.
Backspace
End
Enter
Home
Move Left
Move Right
Move Down
Page Up
Page Down
No visible error message or error condition
is displayed.
Sort Alarm
Reset Alarm
Alarm Banner
Alarm Status List
No visible error message or error condition
is displayed.
Display Print No visible error message or error condition
is displayed.
Trend This object appears not to have any pens
and does not perform real-time trending.
Time and Date No visible error message or error condition
is displayed.
Object Error Mode
Graphic Object Visible Error Mode
IMPORTANT
In Test Display mode, objects in the display are activated and
connected to assigned tags. Only tags connected to objects in
the display will work. Links to other displays or alarms,
including data logging, macros, global connections, and
information messages will not work. Configure communication
to the PLC controller before test running the display or all
objects will show their error states.