Publication 2711P-QS001A-EN-P - October 2007 61
Review Unsupported Features and Implement Workarounds for Migration Issues Chapter 6
3. Double-click the local
message display to open its
properties.
4. Set the Border style to
None.
When you group the local
message displays they will
look as one object with a
continuous border.
5. Set the Back color to match
the background color of the
PanelBuilder 1400e local
message object list.
6. Set the Fore color to match
the foreground color of the
PanelBuilder 1400e local
message object list.
7. Set the Font to match the
font used in the
PanelBuilder 1400e
application.
8. Click the ... button under
Message File to select the
‘LocalMsg’ file that was
converted from your
PanelBuilder 1400e
application.
The local message file
contains all of the strings
that will display in the local
message display as the
operator navigates through
the piloted control list
selector.
IMPORTANT
Use the same font for each local message display so that the
captions align properly with the cursor of the piloted control list
selector. When all message displays are properly aligned,
navigate up and down the piloted control list selector to verify
that the cursor aligns with each local message string.
TIP
FactoryTalk View ME software supports multiple local message
files . To improve screen performance you want to create new
local message files from the migrated “LocalMsg” file. You can
link the new message files to the local message objects instead
of having every local message object parse a large file which
decreases screen performance.