66 Publication 2711P-QS001A-EN-P - October 2007
Chapter 6 Review Unsupported Features and Implement Workarounds for Migration Issues
10. Click the Connections tab.
The PanelBuilder 1400e
numeric data display object
list lets you configure the
number of visible states. For
each visible state, you then
define an associated tag
connection.
Because FactoryTalk View
ME does not support a
numeric data display object
list, you must assign each of
the ‘Visible State x from
PLC’ connections to a single
numeric display object.
Create as many numeric
displays as there are visible
states.
11. Assign the ‘Visible State 1
from PLC’ associated tag to
the Value connection.
12. Click OK to accept changes.
13. Select the numeric display
object and press Ctrl+C to
copy the object.
14. Press Ctrl+V to paste the
copied object.
15. Repeat steps 11 and 12 until
number of pasted numeric
displays matches the
number of visible states in
the original PanelBuilder
1400e object.
FactoryTalk View Object
Original PanelBuilder 1400e Object
Page view 65