Rockwell Automation Publication 193-UM011A-EN-P - September 2010 105
Chapter
10
Using DeviceLogix™
Introduction
DeviceLogix is a stand-alone Boolean program which resides within the EC4
Current Monitoring Relay. RSNetworx for DeviceNet is required to program the
device; however, since the program is embedded in the EC4 software, no
additional module is required to use this technology. It is important to note that
the DeviceLogix program will only run if the logic has been enabled, which can
be done within the Logic Editor of RSNetWorx for DeviceNet or the DeviceNet
Configuration Terminal (Cat. No. 193-DNCT).
In addition to executing specific Boolean logic, DeviceLogix can also be used to
provide specific output performance under specific communcation or network
conditions. This can be accomplished by properly configuring Comm Override
and Network Override parameters.
Comm Override. The configuration of the Comm Override parameter
defines whether or not DeviceLogix controls the EC4 outputs when either
a Comm Fault (lack of I/O connection) or Comm Idle (Master not in Run
mode) condition exists. If DeviceLogix is enabled but Comm Override is
disabled (default), the operation of the EC4 outputs will be controlled by
the DeviceNet Fault State, Fault Value, Idle State, and Idle Value
parameters if a Comm Fault or Comm Idle condition occurs. If
DeviceLogix and Comm Override are both enabled, the EC4 outputs are
controlled by the DeviceLogix program, regardless of the Comm Fault or
Comm Idle state. If DeviceLogix is not enabled, the outputs will be
controlled by the DeviceNet Fault/Idle State/Value parameters if a Comm
Fault or Comm Idle condition occurs – regardless of the Comm Override
configuration. If DeviceLogix is transitioned from enable to disable, the
outputs will immediately go to the programmed DeviceNet Idle
State/Value.
Network Override. The configuration of the Network Override
parameter defines whether or not DeviceLogix controls the EC4 outputs
when a network fault, such as a duplicate Mac ID or bus off condition,
exists. If DeviceLogix is enabled but Network Override is disabled
(default), the operation of the EC4 outputs will be controlled by the
DeviceNet Fault State and Fault Value parameters if a network fault
occurs. If DeviceLogix and Network Override are both enabled, the EC4
outputs are controlled by the DeviceLogix program, regardless of the
network status. If DeviceLogix is not enabled, the outputs will be
controlled by the DeviceNet Fault/Idle State/Value parameters if a Comm
Fault condition occurs – regardless of the Network Override configuration.
If DeviceLogix is transitioned from enable to disable, the outputs will
immediately go to the programmed DeviceNet Idle State/Value.