50 Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 4 DeviceNet Node Commissioning
3. Select “OK”.
4. RSNetWorx notifies the user to upload or download devices before
viewing configuration. Select “OK.
5. RSNetWorx now browses the network and displays all of the nodes it has
detected on the network. For some versions of RSNetWorx software, the
Series B and later EC4 Current Monitoring Relay EDS files may not be
included, and the device will be identified as an “Unrecognized Device”.
If the screen appears like the example in Figure 25 -, continue with Building and
Registering an EDS file.
Figure 25 - Network Online Screen
6. If RSNetWorx recognizes the device as an EC4 Current Monitoring Relay,
skip ahead to the following section – Using the Node Commissioning Tool
of RSNetWorx for DeviceNet.
Building and Registering an EDS File
The EDS file defines how RSNetWorx for DeviceNet will communicate to the
EC4 Current Monitoring Relay. The EDS file can be created over the DeviceNet
network or downloaded from the Internet.
TIP
DeviceNet drivers must be configured using RSLinx prior to being
available to RSNetWorx.
TIP
Node Comisisoning can also be accomplished by using the DeviceNet
Configuration Terminal, Cat. No. 193-DNCT.