52 Rockwell Automation Publication 193-UM011A-EN-P - September 2010
Chapter 4 DeviceNet Node Commissioning
Figure 27 - Setting Default I/O Assembly Sizes
10. Next to the selected Polled check box, do the following:
a. Type 8 in Input Size.
b. Type 1 in Output Size.
11. Select “Next”. RSNetWorx uploads the EDS file from the EC4 Current
Monitoring Relay.
12. To display the icon options for the node, select “Next”.
13. Select the EC4 Current Monitoring Relay icon by highlighting it and
clicking “Change Icon.
14. After selecting the desired icon, select “OK”.
15. Select “Next”.
16. When prompted to register this device, select “Next”.
17. Select “Finish. After a short time, RSNetWorx updates the online screen
by replacingUnrecognized Device” with the name and icon given by the
EDS file that you have just registered.
Using the Node Commissioning Tool of RSNetWorx for DeviceNet
1. From the Tools menu at the top of the screen, select “Node
Commissioning.
2. Select “Browse”.