Rockwell-automation 22-COMM-C ControlNet Adapter User Manual Page 65

  • Download
  • Add to my manuals
  • Print
  • Page
    / 164
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 64
Using Explicit Messaging 6-5
Table 6.A Tags for the ControlLogix Example Explicit Messaging Program
Ladder Logic Program
Figure 6.4 Example ControlLogix Ladder Logic Explicit Messaging Program
For a ControlLogix controller I/O ladder example program, see
Figure 5.3
.
Tag Names
for Read Message Type
Tag Names
for Write Message Type
Perform_Parameter_Read BOOL Perform_Parameter_Write BOOL
Parameter_Read_Message MESSAGE Parameter_Write_Message MESSAGE
Output_Current INT Accel_Time_1 INT
Explicit Messaging Examples
Reading a single parameter (Get Attribute Single command)
This message example reads from Parameter d003 - [Output Current] and stores its value in the "Output_Current" controller
tag.
0
Perform_Parameter_Read
EN
DN
ER
Type - CIP Generic
Message Control Parameter_Read_Message
...
MSG
Explicit Messaging Examples
Reading a single parameter (Get Attribute Single command)
This message example reads from Parameter d003 - [Output Current] and stores its value in the "Output_Current" controller
tag.
Writing a single parameter (Set Attribute Single command)
This message example writes to Parameter P039 - [Accel Time 1] and stores its value in the "Accel_Time_1" controller tag.
1
Perform_Parameter_Write
EN
DN
ER
Type - CIP Generic
Message Control Parameter_Write_Message
...
MSG
Writing a single parameter (Set Attribute Single command)
This message example writes to Parameter P039 - [Accel Time 1] and stores its value in the "Accel_Time_1" controller tag.
(End)