Rockwell-automation 2711 Standard PanelView Operator Terminal User Man User Manual Page 250

  • Download
  • Add to my manuals
  • Print
  • Page
    / 292
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 249
250 Publication 2711-UM014G-EN-P - September 2008
Appendix B Messages, Codes and Self-test Numbers
General Terminal
Messages
Error Number Terminal
Messages
Type Meaning Recommended Action
200-206, 300,
318-321, 328,
329, 331, 346,
347, 355, 356,
358, 367, 404,
411, 416, 417,
421-425,
447-449, 457,
459, 700, 1105,
1111, 1113, 1115,
1207-1211,
2002-2009, 2016,
2018, 2021, 2028
and 2029
A fault has
occurred. Error =
X
Minor Fault
or
Terminal Fault
A minor fault was detected that could
impact terminal operation or a
terminal fault was detected.
Press any key to recover from a minor
fault. For terminal faults, contact
technical support with the error code.
208 Write to logic
controller failed
Comm Status Controller does not accept data from
the terminal. Controller is not
connected.
Check connections (on remote I/O
units). Verify that controller is in run
mode and not busy. Verify that
controller data files are not in use by
other applications.
303 Aborted. Reminder/File
Transfer Status
The terminal received an abort
command during a file transfer.
Try again.
304 File read access
error
Reminder Error reading the source file from a
source device.
Try again. If problem continues,
contact technical support.
305 File write access
error
Reminder Error writing source file. Try again. If problem continues,
contact technical support.
307 File not
supported
Reminder/File
Transfer Status
File is incompatible with the
terminal’s firmware.
Contact technical support to verify
compatibility. File must be a .PVA file.
308 Timeout Reminder / File
Transfer Status
The terminal was waiting for the
partner device in a file transfer, but
the terminal timed out before the
data or expected reply was received.
Check cable connections or data
corruption with noise on cable. Verify
that the computer was not reset. Try
again.
309-311 Data corrupted.
Verify file and
retry.
Reminder/File
Transfer Status
The data checksum failed in a file
transfer.
Check electrical and cable
connections. Try the file transfer
again.
312 Unknown device Reminder / File
Transfer Status
Verify the file type entered. Try again. Destination or source device is invalid
for a read or write application
transfer.
313 File too large Reminder / File
Transfer Status
Reduce application size. See
Appendix A for terminal
requirements. If copying to a card,
check card space.
File too large to be transferred to the
terminal. In a memory card transfer,
the card does not have enough space.
314 No Card Inserted Reminder Install a memory card and try again. You tried to transfer data to/from a
memory card but there is no card in
the card slot.
Page view 249
1 2 ... 245 246 247 248 249 250 251 252 253 254 255 ... 291 292

Comments to this Manuals

No comments