Appendix C European Union Directive Compliance
Intended Use of Product
According to these Standards, the factor which determines, for EMC
purposes, whether a product is deemed to be Industrial rather than
Residential, commercial or light industrial, is given in clause 1 of
EN50081-2 as follows:
Apparatus covered by this standard is not intended for
connection to a public mains network supplied from a high- or
medium-voltage transformer dedicated for the supply of an
installation feeding a manufacturing or similar plant.
When installed in Europe, any other application is in contravention of
European Union Directives, and a breach of these laws.
The PanelView 900 color, the 1000 grayscale and the 1400 terminals
are certified for direct connection to a low-voltage public mains
supply or to a dedicated source, which is intended to interface to a
low-voltage public mains supply.
Wiring Recommendations
To reduce electrical noise, connect the PanelView terminal to its own
branch circuit. The input power source should be protected by a fuse
or circuit breaker rated no more than 15 amps. Route incoming power
to the PanelView terminal by a separate path from the communication
cable.
Where power and communication lines must cross, they should cross
at right angles. Communication lines can be installed in the same
conduit as low-level dc I/O lines (less than 10 Volts).
Declarations of Conformity
Declarations of Conformity are available for each of the PanelView
terminals at the website http://www.ab.com/support
under Product
Certification.