Alert Type Indicates Recommended Action
603 Critical fault File download error Reset the terminal. If problem occurs again, contact
technical support.
9020 Critical fault An internal fault occurred. Reset the terminal. If problem occurs again, contact
technical support.
ControlNet
Error Codes
Error Type Indicates Recommended Action
1803 Informational The communication device has
completed the request to force
the device into the listen-only
state.
The PanelView was detected as having a duplicate
node address and is in the listen-only mode. Check
the node address (MAC ID) of the devices on the
network to verify that addresses are not duplicated.
1824 Warning The PanelView was forced to a
listen-only state.
Contact technical support.
1826 Warning A fixed tag packet was received
but there is no place to route the
packet. The data packet is
discarded and the error message
is displayed.
Contact technical support.
1828 Warning An attempt was made to open
an unsupported transport class.
Contact technical support.
1829 Warning An attempt was made to open a
Class 1 transport with
application triggering or a Class
3 transport with cyclic
triggering.
Contact technical support.
3333 Warning A connection has timed out. A file transfer was unexpectedly interrupted. Try to
transfer again.