Chapter 5 Programmable Parameters
For Catalog Number 193-EC4ZZ
For Catalog Number 193-EC4ZZ
L2 UC Trip Delay
This parameter allows the installer to
program a time duration for which an under
current condition must exist at the
programmed level prior to the device
tripping.
Parameter Number 112
Access Rule Get/Set
Data Type USINT
Object Mapping 2C
hex
-1-163
Group Advanced Setup
Units 0.1 Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0
L2 UC Warn Level
This parameter sets the under current
warning level for line 2.
Parameter Number 113
Access Rule Get/Set
Data Type UINT
Object Mapping 2C
hex
-1-164
2C
hex
-1-119
Group Advanced Setup
Units 0.01 Amps
1 Amps
Minimum Value 0.20
Maximum Value 5000
Default Value
L3 UC Trip Level
This parameter sets the under current trip
level for line 3.
Parameter Number 114
Access Rule Get/Set
Data Type UINT
Object Mapping 2C
hex
-1-165
2C
hex
-1-186
Group Advanced Setup
Units 0.01 Amps
1 Amps
Minimum Value 0.20
Maximum Value 5000
Default Value
L3 UC Trip Delay
This parameter allows the installer to
program a time duration for which an under
current condition must exist at the
programmed level prior to the device
tripping.
Parameter Number 115
Access Rule Get/Set
Data Type USINT
Object Mapping 2C
hex
-1-166
Group Advanced Setup
Units 0.1 Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0