Rockwell Automation Publication 193-UM011A-EN-P - September 2010 69
Programmable Parameters Chapter 5
➊
For Catalog Number 193-EC4ZZ
➊ For Catalog Number 193-EC4ZZ
L3 UC Warn Level
This parameter sets the under current
warning level for line 3.
Parameter Number 116
Access Rule Get/Set
Data Type UINT
Object Mapping 2C
hex
-1-167
2C
hex
-1-120 ➊
Group Advanced Setup
Units 0.01 Amps
1 Amps ➊
Minimum Value 0.20
Maximum Value 5000
Default Value
OC Inhibit Time
This parameter sets the time in which the
over current protection is inhibited during a
starting sequence.
Parameter Number 117
Access Rule Get/Set
Data Type USINT
Object Mapping 2C
hex
-1-168
Group Advanced Setup
Units Seconds
Minimum Value 0
Maximum Value 250
Default Value 1
L1 OC Trip Level
This parameter sets the over current trip
level for line 1.
Parameter Number 118
Access Rule Get/Set
Data Type UINT
Object Mapping 2C
hex
-1-169
2C
hex
-1-187 ➊
Group Advanced Setup
Units 0.01 Amps
1 Amps ➊
Minimum Value 0.20
Maximum Value 5000
Default Value
L1 OC Trip Delay
This parameter allows the installer to
program a time duration for which an over
current condition must exist at the
programmed level prior to the device
tripping.
Parameter Number 119
Access Rule Get/Set
Data Type USINT
Object Mapping 2C
hex
-1-170
Group Advanced Setup
Units 0.1 Seconds
Minimum Value 0.1
Maximum Value 25.0
Default Value 1.0
Comments to this Manuals