ControlNet Objects C-17
N-Files (Continued)
DSI Port Assignments
PCCC Object (Continued)
DSI Port No. Single Mode Multi-Drive Mode
0 The drive Drive 0
1 The adapter Drive 1
2 The slave Drive 2
3 Not supported Drive 3
4 Not supported Drive 4
5 Not supported The adapter
N-File Description
N41
For Single Mode Only
This N-file lets you read and write control I/O messages. You can write
control I/O messages only when all of the following conditions are true:
The adapter is not receiving I/O from a scanner. For example, there is
no scanner on the network, the scanner is in idle (program) mode, the
scanner is faulted, or the adapter is not mapped to the scanner.
The value of N42:3 is set to a non-zero value.
Write Read
N41:0
N41:1
N41:2
Logic Command Word
Unused
Reference
Logic Status Word
Unused
Feedback
N42 This N-file lets you read and write some values configuring the port.
N42:3 Control Time-out (read/write): Time (in seconds) allowed between
messages to the N41 or N44 file. If the adapter does not receive a
message in the specified time, it performs the fault action configured in its
[Comm Flt Action] parameter.
N42:7 Adapter Port Number (read only): DSI port on the drive to which the
adapter is connected.
N42:8 Peer Adapters (read only): Bit field of devices having Peer capabilities.
Page view 134