Configuring the I/O 4-9
Saving the I/O Configuration to the Bridge
You also need to download the I/O configuration to the bridge. You
should also save the configuration to a file on your computer.
1. Launch RSNetWorx for ControlNet. In the RSNetWorx for
ControlNet window, select File > New to display the New File
screen. Then select “ControlNet Configuration” as the network
configuration type, and click OK.
2. Select Network > Online to display the Browse for Network screen
(Figure 4.11
).
Figure 4.11 Browse for Network Screen
3. Expand the communications path from your computer to the
ControlNet bridge. Figure 4.12
shows our example navigating to
devices that are on a ControlNet network. Depending on the
communication link you are using, the navigation path may be
different. After selecting a valid ControlNet path (for this example,
A, ControlNet), click OK.