Using Multi-Drive Mode 7-23
Figure 7.15 ControlLogix Parameter Read Message Configuration
Figure 7.16 ControlLogix Parameter Write Message Configuration
The Class Code is “ f ” for the CIP Parameter Object and the Attribute is
“1” to select the parameter value. See Appendix C, Parameter Object for
more information. The Instance value is “17411” to access parameter
d003 - [Output Current] and “17447” to access parameter P039 - [Accel
Time 1].
Comments to this Manuals