Installing the PV600 Terminal Chapter 9
4. Install the 4 mounting clips (2 on top, 2 on bottom).
The ends of the clips slide into the slots on the terminal.
5. Tighten the clip mounting screws by hand until the gasket seal
contacts the mounting surface uniformly.
6. Alternately tighten the self-locking nuts or mounting clip screws
until the terminal is held firmly against the panel.
7. Tighten the nuts or screws to a torque of 1.13 Nm (10 lb-in).
Do not over-tighten.
8. Remove protective installation labels over top vents of terminal.
Install 4 mounting clips: Top -
left and right slots Bottom - left
and right slots
Self-Locking Nuts
(4 used, 8 provided)
Mounting Studs
(2 left / 2 right)
PV600 Keypad, Keypad & Touch Screen Terminal
PV600 Touch Screen Terminal
1 Protective installation label
2 Protective installation labels
ATTENTION
Mounting nuts must be tightened to a torque of 1.13 Nm
(10 lb-in) to provide a proper seal and to prevent
potential damage to the terminal. Allen-Bradley
assumes no responsibility for water or chemical damage
to the terminal or other equipment within the enclosure
because of improper installation. A properly installed
terminal has a small gap between the bezel and
enclosure.
ATTENTION
Failure to remove the protective installation label
covering the top vents could result in overheating and
damage to the terminal.