Appendix B Messages, Codes and Self-test Numbers
Error Number Terminal
Messages
Type Meaning Recommended Action
xx,xx,xx
Number depends
on hardware fault
detected.
Communication
Interface Fault
Critical Fault A hardware problem was detected
during power-up. If you ignore
message and display the EtherNet/IP
Communication Screen, the Comm
Status displays “Comms hardware
fault:” without an error number. The
FW revision, serial number and
EtherNet/IP address fields are
displayed.
Contact technical support to have unit
repaired.
770 Buffer overflow Comm Status Internal error occurred. Contact technical support.
771 Buffer underflow Comm Status Internal error occurred. Contact technical support.
1799 Heap partition
empty
Comm Status Internal error occurred. Contact technical support.
16387 Comms not
started yet...
Comm Status The PanelView has not connected to
the network.
Check IP configuration (on the
Communication Setup screen) and
wait for PanelView to connect to the
network.
16388 CIP S/N is not
valid
Critical fault. DC incorrectly configured. Contact technical support.
16389 Out of buffers Critical fault. No buffers are available for read or
write operations.
Contact technical support.
16390 An initial write
failed
Comm Warning Write to Logic Controller on Startup
was configured and on powerup, the
PanelView could not write initial
values to a node's data table address.
or
Write to Logic Controller on Startup
was not configured and the
PanelView was unable to write a
controller. Note: The error is only
displayed on the first write attempt.
Check/define data table address in
the controller.
Check communication connections
and node configuration in the
application.
16391 PV write failed Comm Warning PanelView is communicating with the
controller. The data table address
does not exist.
Check/define data table address in
the controller.
16392 PV write timeout Comm Warning PanelView is not communicating with
the logic controller.
Check connections and node
configuration in the application.
16393 PV read fail Comm Warning PanelView is communicating with the
controller. The data table address
does not exist.
Check/define data table address in
the controller.
16394 PV read timeout Comm Warning PanelView is not communicating with
the controller.
Check/define data table address in
the controller.
16397 CN object
received a reset
request
Comm Warning An Ethernet object received a reset
request from a device on the network.
The PanelView does not support
network resets.