Rockwell Automation Publication 2099-UM001D-EN-P - December 2012 107
Configure and Startup the Kinetix 7000 Drive System Chapter 5
5. Set the SERCOS optical power level to High using DIP switch 1.
Figure 64 - SERCOS DIP Switch Settings and Locations
6. Repeat Steps 4 and 5 for each Kinetix 7000 drive.
For This Optical Power Level Set Switch 1
Low OFF
High ON
IMPORTANT
All drives on the SERCOS ring must have the same baud rate and power setting.
1 2 3
1 2 3
DIP Switches Set for
4 Mbps Applications
(high-power setting)
DIP Switches Set for
8 Mbps Applications
(high-power setting)
ON
OFF
SERCOS Baud Rate
and Optical Power Switches
SERCOS switch and connectors
(typical orientation around DPI connector)
ON
OFF
Switch in ON Position
Switch in OFF Position
Note: 8 Mbps setting shown.