128 Rockwell Automation Publication 2099-UM001D-EN-P - December 2012
Chapter 5 Configure and Startup the Kinetix 7000 Drive System
5. Observe the three status indicators on the front of the drive.
6. Observe the three SERCOS status indicators on the SERCOS module.
Status Indicator Condition Status Do This
Drive
Off Normal condition Observe the Comm status LED.
Steady red Drive is faulted Go to Status Indicators on page 143.
Comm
Flashing green Establishing communication with network Wait for steady green.
Steady green Communication is ready Observe the Bus status LED
Off No ring present Go to Interpret Error Codes and Status Indicators on page 138
.
Bus
Steady green Axis is enabled when status should be disabled
1. Verify Hardware Enable Input (IOD-2) is open.
2. Verify MSO instruction is not commanded in RSLogix 5000
software.
3. Return to Apply Power to the Drive on page 126.
Flashing green
(1)
Bus is up, axis is disabled (normal status) Go to step 6.
Off DC bus is not present Go to Status Indicators on page 143.
(1) The follower drive has a 2.5 second delay after DC bus voltage is applied before the Bus Status LED begins flashing. This provides the common bus leader time to complete precharge.
SERCOS Status Indicators Status Do This
Flashing green and red Establishing communication Wait for steady green on all three LEDs.
Steady green Communication is ready Go to Test and Tune the Axes on page 129
.
Not flashing green and red/
not steady green
SERCOS module is faulted
Go to the appropriate Logix manual for specific
instructions and troubleshooting.