Rockwell Automation 1785 PLC-5 User Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 172
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
Hardware Components
Processor Comparison 1-8
PLC-5 comparison chart continued...
Processor Memory
(Words)
Local
Chassis
Remote Chassis
(I/O Racks)
I/O Capacity Communication
PLC-5/40
48K
3
1 resident
60
2
(15 I/O racks)
2048
1
2048 inputs and 2048 outputs using 16-
or 32-pt modules
4 channels (remote I/O scanner, adapter, DH+ link)
1 RS-232, RS-422, RS-423 serial port
PLC-5/40L
48K
3
1 resident up
to 16
extended
60
2
(15 I/O racks)
2048
1
2048 inputs and 2048 outputs using 16-
or 32-pt modules
2 channels (remote I/O scanner, adapter, DH+ link)
1 RS-232, RS-422, RS-423 serial port
1 channel extended local I/O scanner
PLC-5/40E
48K
3
1 resident
(16 rack
addressing
capability)
60
(15 I/O racks)
2048
1
2048 inputs and 2048 outputs using 16-
or 32-pt modules
2 channels (remote I/O scanner, adapter, DH+ link)
1 RS-232, RS-422, RS-423 serial port
1 channel Ethernet
PLC-5/40C15
48K
3
1 resident 60
15 I/O racks
2048
1
2048 inputs and 2048 outputs using 16-
or 32-pt modules
2 channels (remote I/O scanner, adapter, DH+ link)
1 RS-232, RS-422, RS-423 serial port
1 channel ControlNet
PLC-5/60
3
64K 1 resident
92
2
(23 I/O racks)
3072
1
3072 inputs and 3072 outputs using 16-
or 32-pt modules
4 channels (remote I/O scanner, adapter, DH+ link)
1 RS-232, RS-422, RS-423 serial port
1
Any mix of I/O
2
Maximum of 32 physical devices/channel
3
Maximum of 57K words per program file and 32K words per data table file