Processor Status File 1-21
processor status file continued...
This word of the status file: Stores:
S:12 continued... Fault codes
Code Description
88 scanner channels are overloading the remote I/O buffer; too much data for the
processor to process
90 Sidecar module extensive memory test failed
91 Sidecar module undefined message type
92 Sidecar module requesting undefined pool
93 Sidecar module illegal maximum pool size
94 Sidecar module illegal ASCII message
95 Sidecar module reported fault, which may be the result of a bad
program that corrupts memory or of a hardware failure
96 Sidecar module not physically connected to the PLC-5 processor
97 Sidecar module requested a pool size that is too small for PCCC command (occurs at power-up)
98 Sidecar module first/last 16 bytes RAM test failed
99 Sidecar module-to-processor data transfer faulted
100 Processor-to-sidecar module data transfer failed
101 Sidecar module end of scan data transfer failed
102 The file number specified for raw data transfer through the sidecar
module is an illegal value
103 The element number specified for raw data transfer through the
sidecar module is an illegal value
104 The size of the raw data transfer requested through the sidecar module is an illegal size
105 The offset into the raw data transfer segment of the sidecar module is an illegal value